18/30kv Medium Voltage Single Core Copper XLPE Power Cable

Model NO.: 185mm2
Wire Core Material: Bare Copper Wire
Certification: ISO, CCC
Model: YJLV22
Brand: Jytop
Standard: ASTM, AS/NZS, BS, CSA, DIN, IEC...
Certificate: Ce, ISO 9001
Rated Voltage: High Voltage Cable
Core Number: Single Core Cable
Color: Black
Trademark: JYTOP
Transport Package: Packed in Reels
Specification: based on ASTM or IEC or BS or NF standards
Origin: Zhengzhou, China
HS Code: 8544601200
Model NO.: 185mm2
Wire Core Material: Bare Copper Wire
Certification: ISO, CCC
Model: YJLV22
Brand: Jytop
Standard: ASTM, AS/NZS, BS, CSA, DIN, IEC...
Certificate: Ce, ISO 9001
Rated Voltage: High Voltage Cable
Core Number: Single Core Cable
Color: Black
Trademark: JYTOP
Transport Package: Packed in Reels
Specification: based on ASTM or IEC or BS or NF standards
Origin: Zhengzhou, China
HS Code: 8544601200
18/30kV Medium voltage MV copper conductor XLPE insulation aluminum wire armored power cable

1. Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, galvanized steel wire armored, PVC or PE outer sheath.

2. Operating Characteristics
Rated voltage U0/U(Um): 18/30(36)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 15 times of the diameter of cable
For three core cable: Not less than 12 times of the diameter of cable
When the armored single core cable used for Alternative Current(AC) system, the armoring material should be non-magnetic.

3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel, in cable trench, or direct in ground, able to bear external mechanical force and certain pulling force.

4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.

18/30kv Medium Voltage Single Core Copper XLPE Power Cable

Main technical data of cable18/30KV CU/XLPE/AWA/PVC or PE
 
 
Size
Nominal thickness of XLPE insulation(mm) Approx. thickness of copper tape screen (mm) Approx. diameter  of armoring pure aluminum wire(mm) Nominal thickness of PVC or PE(mm) Approx. overall diameter of finished cable(mm) Max. conductor D.C resistance @ 20 0 C (Ω/km)
1x50mm 2 8.0 0.12 2.0 2.2 39.2 0.387
1x70mm 2 8.0 0.12 2.0 2.2 40.9 0.268
1x95mm 2 8.0 0.12 2.0 2.3 42.7 0.193
1x120mm 2 8.0 0.12 2.0 2.3 44.1 0.153
1x150mm 2 8.0 0.12 2.5 2.4 46.9 0.124
1x185mm 2 8.0 0.12 2.5 2.5 48.9 0.0991
1x240mm 2 8.0 0.12 2.5 2.5 51.3 0.0754
1x300mm 2 8.0 0.12 2.5 2.6 53.7 0.0601
1x400mm 2 8.0 0.12 2.5 2.7 57.1 0.0470
1x500mm 2 8.0 0.12 2.5 2.8 61.2 0.0366
1x630mm 2 8.0 0.12 2.5 2.9 65.0 0.0283
1x800mm 2 8.0 0.12 2.5 3.1 69.4 0.0221

18/30kv Medium Voltage Single Core Copper XLPE Power Cable

18/30kv Medium Voltage Single Core Copper XLPE Power Cable

  18/30kV Medium voltage MV copper conductor XLPE insulation aluminum wire armored power cable

1. Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, galvanized steel wire armored, PVC or PE outer sheath.

2. Operating Characteristics
Rated voltage U0/U(Um): 18/30(36)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 15 times of the diameter of cable
For three core cable: Not less than 12 times of the diameter of cable
When the armored single core cable used for Alternative Current(AC) system, the armoring material should be non-magnetic.

3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel, in cable trench, or direct in ground, able to bear external mechanical force and certain pulling force.

4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.

18/30kv Medium Voltage Single Core Copper XLPE Power Cable

Main technical data of cable18/30KV CU/XLPE/AWA/PVC or PE
 
 
Size
Nominal thickness of XLPE insulation(mm) Approx. thickness of copper tape screen (mm) Approx. diameter  of armoring pure aluminum wire(mm) Nominal thickness of PVC or PE(mm) Approx. overall diameter of finished cable(mm) Max. conductor D.C resistance @ 20 0 C (Ω/km)
1x50mm 2 8.0 0.12 2.0 2.2 39.2 0.387
1x70mm 2 8.0 0.12 2.0 2.2 40.9 0.268
1x95mm 2 8.0 0.12 2.0 2.3 42.7 0.193
1x120mm 2 8.0 0.12 2.0 2.3 44.1 0.153
1x150mm 2 8.0 0.12 2.5 2.4 46.9 0.124
1x185mm 2 8.0 0.12 2.5 2.5 48.9 0.0991
1x240mm 2 8.0 0.12 2.5 2.5 51.3 0.0754
1x300mm 2 8.0 0.12 2.5 2.6 53.7 0.0601
1x400mm 2 8.0 0.12 2.5 2.7 57.1 0.0470
1x500mm 2 8.0 0.12 2.5 2.8 61.2 0.0366
1x630mm 2 8.0 0.12 2.5 2.9 65.0 0.0283
1x800mm 2 8.0 0.12 2.5 3.1 69.4 0.0221

18/30kv Medium Voltage Single Core Copper XLPE Power Cable

18/30kv Medium Voltage Single Core Copper XLPE Power Cable

 

Powerful LED Diving Flashlight

Led Flashlight,Diving Flashlight,Led Flashlight

Thefirst International Lighting Co., Ltd. , http://www.gddivinglight.com